Supply External supply for digital inputs: 24 V DC (19…30V), <1.25mA, protection type: overload and short-
circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10mA, protection
type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27V), <200mA, protection type: overload
and short-circuit protection
Local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width 171mm
Height 409mm
Depth 233mm
Net weight 7.7kg
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12
bits
Discrete input number 8
Discrete input type DI1...DI6 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30kHz, 24 V DC (<= 30 V)
STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Discrete input logic Positive logic (source) (DI1...DI6), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1)
Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
Analogue output number 2
Analogue output type Software-configurable voltage AO1, AO2: 0...10 V DC impedance 470Ohm, resolution 10 bits
Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits
Sampling duration 2ms +/- 0.5 ms (DI1...DI4) - discrete input
5ms +/- 1 ms (DI5, DI6) - discrete input
5ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10ms +/- 1 ms (AO1) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current Relay output R1, R2, R3: 5mA at 24 V DC
Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7ms: 2A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7ms: 2A at 30 V DC
Isolation Between power and control terminals
Variable speed drive application
selection
Compressor centrifugal Building - HVAC
Other application Food and beverage processing
Fan Mining mineral and metal
Pump Mining mineral and metal
Fan Oil and gas
Other application Water and waste water
Screw compressor Building - HVAC
Pump Food and beverage processing
Fan Food and beverage processing
Atomization Food and beverage processing
Electro submersible pump (ESP) Oil and gas
Water injection pump Oil and gas
Jet fuel pump Oil and gas
Compressor for refinery Oil and gas
Centrifuge pump Water and waste water
3