Product data sheet
Characteristics ATV630D11N4
variable speed drive ATV630, 11kW/15HP,
380...480V, IP21/UL type 1
Main
Range of product Altivar Process ATV600
Product or component type Variable speed drive
Product specific application Process and utilities
Device short name ATV630
Variant Standard version
Product destination Synchronous motors
Asynchronous motors
EMC filter Integrated with 50m conforming to EN/IEC 61800-3 category C2
Integrated with 150m conforming to EN/IEC 61800-3 category C3
IP degree of protection IP21 conforming to IEC 61800-5-1
IP21 conforming to IEC 60529
Degree of protection UL type 1 conforming to UL 508C
Type of cooling Forced convection
Supply frequency 50...60 Hz - 5...5 %
[Us] rated supply voltage 380...480 V - 15...10 %
Motor power kW 11kW (normal duty)
7.5kW (heavy duty)
Motor power hp 15hp normal duty
10hp heavy duty
Line current 19.8A at 380 V (normal duty)
17A at 480 V (normal duty)
14.1A at 380 V (heavy duty)
12.5A at 480 V (heavy duty)
Prospective line Isc 50kA
Apparent power 14.1kVA at 480 V (normal duty)
10.4kVA at 480 V (heavy duty)
Continuous output current 23.5A at 4 kHz for normal duty
16.5A at 4 kHz for heavy duty
Maximum transient current 25.9A during 60 s (normal duty)
24.8A during 60 s (heavy duty)
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Feb 23, 2021
1
Asynchronous motor control profile Constant torque standard
Optimized torque mode
Variable torque standard
Synchronous motor control profile Permanent magnet motor
Synchronous reluctance motor
Output frequency 0.0001…0.5kHz
Speed drive output frequency 0.1…599Hz
Nominal switching frequency 4 kHz
Switching frequency 2...12 kHz adjustable
4...12 kHz with derating factor
Safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds
Communication port protocol Modbus TCP
Ethernet
Modbus serial
Option card Slot A: communication module, Profibus DP V1
Slot A: communication module, Profinet
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/EtherNet/IP
Slot A: communication module, CANopen daisy chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw terminals
Slot A/slot B: digital and analog I/O extension module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink
Complementary
Mounting mode Wall mount
Output voltage <= power supply voltage
Permissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Motor slip compensation Adjustable
Can be suppressed
Not available in permanent magnet motor law
Automatic whatever the load
Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s
Braking to standstill By DC injection
Protection type Thermal protection: motor
Safe torque off: motor
Motor phase break: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and earth: drive
Overload of output voltage: drive
Short-circuit protection: drive
Motor phase break: drive
Overvoltages on the DC bus: drive
Line supply overvoltage: drive
Line supply undervoltage: drive
Line supply phase loss: drive
Overspeed: drive
Break on the control circuit: drive
Frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Electrical connection Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
Motor: screw terminal 6...10 mm²/AWG 10...AWG 8
Line side: screw terminal 6 mm²/AWG 10
Connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses 1…247 for Modbus serial
Method of access Slave Modbus TCP
2
Supply External supply for digital inputs: 24 V DC (19…30V), <1.25mA, protection type: overload and short-
circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10mA, protection
type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27V), <200mA, protection type: overload
and short-circuit protection
Local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Width 171mm
Height 409mm
Depth 233mm
Net weight 7.7kg
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12
bits
Discrete input number 8
Discrete input type DI1...DI6 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30kHz, 24 V DC (<= 30 V)
STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Discrete input logic Positive logic (source) (DI1...DI6), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1)
Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
Analogue output number 2
Analogue output type Software-configurable voltage AO1, AO2: 0...10 V DC impedance 470Ohm, resolution 10 bits
Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits
Sampling duration 2ms +/- 0.5 ms (DI1...DI4) - discrete input
5ms +/- 1 ms (DI5, DI6) - discrete input
5ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10ms +/- 1 ms (AO1) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000cycles
Configurable relay logic R2: sequence relay NO electrical durability 100000cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current Relay output R1, R2, R3: 5mA at 24 V DC
Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7ms: 2A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7ms: 2A at 30 V DC
Isolation Between power and control terminals
Variable speed drive application
selection
Compressor centrifugal Building - HVAC
Other application Food and beverage processing
Fan Mining mineral and metal
Pump Mining mineral and metal
Fan Oil and gas
Other application Water and waste water
Screw compressor Building - HVAC
Pump Food and beverage processing
Fan Food and beverage processing
Atomization Food and beverage processing
Electro submersible pump (ESP) Oil and gas
Water injection pump Oil and gas
Jet fuel pump Oil and gas
Compressor for refinery Oil and gas
Centrifuge pump Water and waste water
3
Positive displacement pump Water and waste water
Electro submersible pump (ESP) Water and waste water
Screw pump Water and waste water
Lobe compressor Water and waste water
Screw compressor Water and waste water
Compressor centrifugal Water and waste water
Fan Water and waste water
Conveyor Water and waste water
Mixer Water and waste water
Motor power range AC-3 7…11kW at 380…440V 3 phases
7…11kW at 480…500V 3 phases
Environment
Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Noise level 56dB conforming to 86/188/EEC
Power dissipation in W Natural convection: 51W at 380 V, switching frequency 4 kHz
Forced convection: 255W at 380 V, switching frequency 4 kHz
Volume of cooling air 103m3/h
Operating position Vertical +/- 10 degree
Maximum THDI <48% from 80...100 % of load conforming to IEC 61000-3-12
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree 2 conforming to EN/IEC 61800-5-1
Vibration resistance 1.5 mm peak to peak (f= 2…13Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn for 11ms conforming to IEC 60068-2-27
Relative humidity 5…95% without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation -15…50°C (without derating)
50…60°C (with derating factor)
Ambient air temperature for storage -40…70°C
Operating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
Standards UL 508C
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Product certifications ATEX INERIS
CSA
UL
ATEX zone 2/22
DNV-GL
TÜV
Marking CE
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 10.467kg
Package 1 Height 35cm
Package 1 width 21.5cm
Package 1 Length 58cm
Unit Type of Package 2 P06
Number of Units in Package 2 3
4
Package 2 Weight 44.4kg
Package 2 Height 80cm
Package 2 width 80cm
Package 2 Length 60cm
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Upgradeability Upgraded components available
5
Product data sheet
Dimensions Drawings ATV630D11N4
Dimensions
Drives with IP21 Top Cover
Front and Left Views
Drives Without IP21 Top Cover
Left and Rear Views
6
Product data sheet
Mounting and Clearance ATV630D11N4
Clearances
X1 X2 X3
≥ 100 mm (3.94 in.) ≥ 100 mm (3.94 in.) ≥ 10 mm (0.39 in.)
7
Product data sheet
Mounting and Clearance ATV630D11N4
Mounting Types
Mounting Type A: Individual IP21
a ≥ 100 mm (3.94 in.)
Mounting Type B: Side by Side IP20
Mounting Type C: Individual IP20
a ≥ 0
8
Product data sheet
Connections and Schema ATV630D11N4
Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
(1) Line choke if used
(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Line Contactor
Q2, Q3 : Circuit breakers
S1, S2 : Pushbuttons
T1 : Transformer for control part
9
Product data sheet
Connections and Schema ATV630D11N4
Three-Phase Power Supply with Downstream Breaking via Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1
(1) Line choke if used
(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Contactor
10
Product data sheet
Connections and Schema ATV630D11N4
Control Block Wiring Diagram
(1) Safe Torque Off
(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
R1A, R1B, R1C :Fault relay
R2A, R2C :Sequence relay
R3A, R3C :Sequence relay
Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
11
Product data sheet
Connections and Schema ATV630D11N4
Sink / Source Switch Configuration
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs
Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs
Switch Set to EXT Position Using an External Power Supply for the DIs
12
Product data sheet
Performance Curves ATV630D11N4
Derating Curves
40 °C (104 °F) - Mounting type A, B and C
50 °C (122 °F) - Mounting type A, B and C
60 °C (140 °F) - Mounting type B and C
In : Nominal Drive Current
SF : Switching Frequency
13