Specifications are subject to change without notice (18.01.2010) 3
RMD3H48HA40
Connection Specifications
Connection Type Power Connection Screw terminal Control Connection FASTON terminal
Illustration of terminal
Terminal Designations 1L1, 2T1, 3L2, 4T2, 5L3, 6T3, 7N A1, A2
Rigid (Solid or Stranded) 1 x (2.5-16)mm² N/A
1 x (14-6)AWG
Tightening torque 18 in lb (2.1Nm) N/A
Size No. 10 screw 6.35mm (1/4 inch) FASTON
Aperture for termination lug Max 13.5mm for ring and fork/spade termination lugs
Weight approx. 360g
Housing Material PA66
Flame class UL94V0
Dimensions (w x h x d)
(without input connector) 105 x 45 x 90 mm
Housing Specifications
Operating Temperature 0 to 70°C
Storage Temperature 0 to 100°C
Humidity 95% RH, non condensing @ 40°C
Impact resistance 15/11 g/ms
Environmental Specifications
CE marking
Low Voltage Directive IEC / EN 60947-4-3
EMC Immunity IEC / EN 61000-6-3
EMC Emission IEC / EN 61000-6-1
Electrostatic Discharge (ESD)
Immunity IEC / EN 61000-4-2
8kV, PC2 Air discharge
4kV, PC2 Contact
Electrical Fast Transient
Burst Immunity IEC / EN 61000-4-4
Output 2kV, performance criteria 1
Input 1kV, performance criteria 1
Electrical Surge Immunity IEC / EN 61000-4-5
Output, line to line 1kV, performance criteria 1
Output, line to earth 2kV, performance criteria 1
Input, line to line 1kV, performance criteria 2
Intput, line to earth 2kV, performance criteria 2
Radio Interference field IEC / EN 55011
emissions (radiated) Class B (light industry)
Approvals cURus (E80573)
Endurance Test 100,000 cycle as per UL508
Restrictions of hazardous
substances RoHS
Radiated Radio Frequency
Immunity EN 61000-4-3
10 V/m, 80 - 1000 MHz,
1.4 - 2.0 GHz Performance criteria 1
1 V/m, 2.0 - 2.7 GHz Performance criteria 1
Conducted Radio Frequency
Immunity IEC / EN 61000-4-6
10V/m, 0.15 - 80 MHz Performance criteria 1
Voltage Dips Immunity IEC / EN 61000-4-11
0% for 10ms/20ms,
70% for 500ms Performance criteria 2
40% for 200ms Performance criteria 3
Voltage Interruptions Immunity IEC / EN 61000-4-11
0% for 5000ms Performance criteria 3
Radio Interference voltage EC / EN 55011
emissions (conducted) Class A (industrial)
Agency Approvals & EMC